Tampilkan postingan dengan label Sains Arsitektur. Tampilkan semua postingan
Tampilkan postingan dengan label Sains Arsitektur. Tampilkan semua postingan

Jumat, 17 April 2015

materi kuliah sains arsitektur minggu VII

PERHITUNGAN BEBAN PENDINGINAN

Estimation (Juwana, 2005)

No
Component
Formula
Annotation
1
Level of occupancy (occ)
Occ = Lbruto/Lper-person
You can also count by standard
Lbruto = total floor area
Lper-person = 15-20
2
Envelope / building sensible heat load (BSL)
BSL = Lsurface x HL
Lsurface = area of bldg element
HL = heat load of bldg component
3
Internal load:
Sensible and laten of the occupant (OSL, OLL)
Sensible heat load of lamps (LSL)
OSL = Occ x 200 BTUh
OLL = Occ x 250 BTUh
LSL = (Σ watt) x 1.25 x 3.4 BTUh

4
Infiltration load (CFM1)
CFM1 = (l xw x h x ACH x 35.31) / 60 BTUh

5
Ventilation load
CFM2 = (To-Ti) x1.08 + (RHo-RHi) x 0.67 BTUh
To = temp outdoor
Ti =indoor
Indonesian case, To-Ti=5oC
RHo = outdoor rel humidity
RH i = Indoor rel humidity
6
Cooling Load (CL)
CL = BSL + OSL + OLL + LSL + CFM1 + CFM 2

7
Cooling Capacity (TR)
TR = CL / 12000 BTUh


1TR (ton refrigeration) = 12.000 BTU

1 PK = 9.000 BTU


Cross Check

PK = (A x H)/100 x Koef TR x (12000/900)

Dimana:

PK           = Kebutuhan PK AC
A             = Luas Ruangan
H             = Tinggi Lantai ke Plafond
Koef TR  = 1



TUGAS:
*  Hitung beban pendinginan dan kebutuhan AC di studi kasus anda
*  Gambarkan juga peletakan indoor dan outdoor AC pada denah

Degan asumsi:
To - Ti = 5
Rho - Rhi = 15
Occupancy kelas = 40 orang
Occupancy lab = 15 orang
Occupancy ruang rapat = 20 orang

Tugas dikumpulkan pada saat UTS